businesspress24.com - More safety for large-scale photovoltaic systems
 

More safety for large-scale photovoltaic systems

ID: 1531806

The insulation monitoring device ISOMETER® iso1685P for unearthed AC, AC/DC and DC systems (IT systems) up to AC 1000 V/DC 1500 V

(PresseBox) - The devices isoPV1685 and isoPV1685P are two of the latest insulation monitoring device for insulation monitoring of large-scale photovoltaic systems up to approx. 2.5 megawatts and a system leakage capacitance of 2000

At a supply voltage of DC 18?30 V the devices have a low power consumption of ? 7.5 VA.

By using the latest measuring technology it is possible, despite very high-impedance coupling (Ri ? 70 k?) and low coupled measuring current (Im ? 1.5 mA), to realise an extremely wide range for the insulation fault response value (Ran = 200 ? ? 1 M?).

The insulation fault location feature included in the isoPV1685P is a device feature that will pay for itself very quickly in large-scale PV systems. In the event of an insulation fault being reported by the insulation monitoring, the internal locating current injector is activated automatically or manually on the PV system without any changes; both the faulty string and the faulty module can then be located very quickly in the large-scale PV system with the aid of an already installed and/or portable insulation fault locator (e.g. EDS460-D or EDS195P), without the need to take parts of the installation out of operation to locate the fault. By using the integrated insulation fault location function in the isoPV1685P variant, costs for insulation fault location by electricians and the related downtimes can be saved.

Along with the three alarm relays, the device features the Bender-specific BMS bus as a digital interface and also a CAN bus.

A further innovative feature of the isoPV1685P variant is the data logger function for proactive installation maintenance and a history memory for alarms on an integrated ?SD card, without the need for a digital network. By straightforwardly evaluating the text-based files, the data logger function can be used to optimise the uptime of the large-scale PV system monitored and to minimise maintenance costs by means of long-term planning. The history memory is saved in the common .csv format. An Excel tool is available for easy evaluation. With a 2-GByte





Thanks to the complete long-term monitoring with a combined regular graphical evaluation of the insulation resistance value over time, the system operator increases the probability that even hazardous design defects of the large-scale PV system can be detected. For example, if an inappropriate combination of PV connectors is used, it is likely that the poor fit will result in the ingress of dirt and moisture into the connection. In turn, it is highly probable that it will be possible to detect this pollution due to gradual reduction of the insulation resistance in the graphical trend evaluation, even with values above the required response values. As described in the article "Warum kompatible PV-Steckverbinder gef" (Why compatible PV connectors are dangerous) (ELEKTRONIKPRAXIS no. 16 from 26.8.2013), it is exactly these design errors that can result in fires in PV systems.

By using the data logger function on the isoPV1685P, it is highly probable that system states involving "fire risk" on PV installations can be detected at an early stage. Preventive maintenance helps avoiding fire.

Weitere Infos zu dieser Pressemeldung:

Themen in dieser Pressemitteilung:


Unternehmensinformation / Kurzprofil:



Leseranfragen:



PresseKontakt / Agentur:



drucken  als PDF  an Freund senden  Bender receives ''UL Functional Safety Mark'' for its isoPV1685 series insulation monitoring devices
Electrical safety starts in the electrical installation with the compact AC/DC sensitive RCMB104 residual current monitoring module
Bereitgestellt von Benutzer: PresseBox
Datum: 24.01.2018 - 04:12 Uhr
Sprache: Deutsch
News-ID 1531806
Anzahl Zeichen: 2829

contact information:
Contact person:
Town:

Grünberg


Phone:

Kategorie:

Research & Development


Typ of Press Release:
type of sending:
Date of sending:
Anmerkungen:


Diese Pressemitteilung wurde bisher 713 mal aufgerufen.


Die Pressemitteilung mit dem Titel:
"More safety for large-scale photovoltaic systems
"
steht unter der journalistisch-redaktionellen Verantwortung von

Bender GmbH&Co. KG (Nachricht senden)

Beachten Sie bitte die weiteren Informationen zum Haftungsauschluß (gemäß TMG - TeleMedianGesetz) und dem Datenschutz (gemäß der DSGVO).

New, divisible measuring current transformers ...

Bender has added new measuring current transformers to its portfolio that are specifically intended for use in existing electrical installations. The sensors of the CTAS series are divisible and therefore particularly suitable for those installations ...

Bender COMTRAXX?devices ...

The devices of the COMTRAXX? family from Bender GmbH & Co. KG are now even more flexible. With the latest software update, the PROFINET interface has been integrated. It has become the leading standard on the market in recent years. The devices t ...

Electrical safety and high-quality medical technology ...

The Grünberg-based company Bender, specialising in electrical safety, will in future offer medical technology from the Finnish manufacturer Merivaara. Bender expands its hospital portfolio as Merivaara s exclusive sales partner for Germany in order ...