Insulation monitoring for mobile generators with isoGEN523
(PresseBox) - Bender has been a supplier of insulation monitoring devices that are specified for use in mobile power generators for many years. This ISOMETERore loads is described in DIN VDE 0100-410 (VDE 0100-410):2007-06.
With a single load connected to the generator, no further protective measures are required. However, if more than one operating resource is connected to the generator, the requirements of the new section ZC.3.2.2 of DIN VDE 0100-551, issued in February 2017, apply. The protective measure is then to be executed so that an insulation monitoring device (IMD) complying with DIN EN 61557-8:2016-01 is installed between the active conductors and the equipotential bonding. This must continuously monitor the insulation resistance. If the insulation resistance falls below the value of 100 ?/V (230 V - 23 k?), the insulation monitoring device switches the output circuit of the generator or the electrical load off within one second.
When selecting the IMD, it is to be ensured that the measuring technology is suitable for this application. The simplest devices with superimposed DC measuring voltage are usually not able to detect insulation faults with DC components or higher system leakage capacitances. The current IMDs, such as the ISOMETER
The ISOMETER
Unlike its predecessor, the unit is housed in a sealed case and can be connected via a cable in the generator. A port monitor, which is activated when the device is turned on and then hourly by an automatic self-test, detects whether the necessary ports to the generator and the equipotential bonding are still open. This feature is especially important as the device can also be used for high shock and vibration requirements, as well as in a higher temperature range. Even heavy pollution or high humidity are not a problem for the isoGEN523.
The isoGEN523 offers the possibility of system isolation as an additional feature. This means that the IMD automatically disconnects from the monitored power supply in a voltage-free state via integrated switch contacts.
The advantage for the operator is that the coupling resistance of the IMD is no longer present between the generator winding and the equipotential bonding (PE) in an insulation test of the generator by means of an insulation test device. This ensures that the limit value of the test current induced by the insulation test is not exceeded by the ISOMETER
Previous devices of this type such as the ISOMETER
Themen in dieser Pressemitteilung:
Unternehmensinformation / Kurzprofil:
Datum: 24.01.2018 - 02:06 Uhr
Sprache: Deutsch
News-ID 1531787
Anzahl Zeichen: 2456
contact information:
Contact person:
Town:
Grünberg
Phone:
Kategorie:
Research & Development
Typ of Press Release:
type of sending:
Date of sending:
Anmerkungen:
Diese Pressemitteilung wurde bisher 425 mal aufgerufen.
Die Pressemitteilung mit dem Titel:
"Insulation monitoring for mobile generators with isoGEN523
"
steht unter der journalistisch-redaktionellen Verantwortung von
Bender GmbH&Co. KG (Nachricht senden)
Beachten Sie bitte die weiteren Informationen zum Haftungsauschluß (gemäß TMG - TeleMedianGesetz) und dem Datenschutz (gemäß der DSGVO).